ARVOTECH Diesel Engine Fire Pump Controller
General Information
Diesel Engine Fire Pump Controller
Technical Specifications
Operator Interface
- HMI: 7″ Color Touch Screen HMI
- Menu: Password protected configuration menu
- Recording: Data & Event recording with timestamp
- Visuals: Graphical representation of trend graphs
- Languages: Multi-language support including English, Spanish, and French
Standard Features
- Monitoring: Battery Parameters Display for Voltage and Current
- Control Switches: HAND-OFF – AUTO selector switch
- Manual Controls: Manual crank, start, stop, and run test pushbuttons
- Provisions: Remote start and Deluge valve start provisions
- Hardware: Pressure transducer and run test solenoid valve are externally mounted
- Alarms: Audible alarm and alarm contacts for remote indication
- I/O: Five field-programmable inputs and five field-programmable outputs
- Indicators/Alarms:
- Engine Running
- Power Failure
- Controller Trouble
- Engine Trouble
- Pump Room Alarm
Standards & Approvals
- UL218
- FM 1321/1323
- Built to NFPA20 standards
- FM Approved
- CULUS listed
Electrical Ratings
- Supply Voltage: Models available in 120V (110–120) & 230V (220–240)
- Battery Voltage: 12V & 24V
- Frequency: 50/60 Hz
Enclosure & Physical Dimensions
- Type: NEMA Type 2
- Design: Powder-coated lockable enclosure in RAL3002 color
- Mounting: Lifting lugs with foot mount or wall mount arrangement
- Cable Entry: Bottom cable entry with gland plate
- Enclosure Dimensions: 691mm (width with alarm bell), 600mm (box width), 1193mm (total height), and 319mm (depth)
Shipping Data
| Description | Details |
| Packing Dimension | $700 \times 350 \times 1250$ mm |
| Net Weight | 85 kg |
| Gross Weight | 130 kg |