FIRETROL ENGINE FIRE PUMP CONTROL

“Firetrol” Engine Fire pump controller

Firetrol MarkIII+ Diesel Engine Fire Pump Controller

FTA1100J – 12 or 24 Volt

 Standard Features – The following are included as standard with each controller:

  • NEMA Type 2 (IP22) Enclosure with Bottom Entry Gland Plate, Lifting Lugs and Locking Door Handle
  • AC Line & Battery circuit breakers
  • Two independent battery chargers, 10Acontinuous charge – 500mA TrickleCharge
  • 7.0” LCD capacitive type color touch screen (HMI technology) software upgradeable operator interface powered by an embedded microcomputer with software PLC logic.
  • Push-buttons for Crank from Battery #1, Crank from Battery #2, Stop and Run Test
  • 500 PSI Pressure Transducer (calibrated for 300 PSI (20.7 Bar) and Test Solenoid for fresh water applications, externally mounted with protective cover
  • Audible alarm buzzer embedded in the MarkIII+
  • Pressure and Event Recording with Date Stamp to System Memory Accessible VIA The User Interface and Downloadable to a USB Flash Drive

Visual Indication for

  • Engine Run
  • MainSwitch Position
  • Periodic Test
  • Cranking Cycle
  • AC Power Available
  • Pump Room Temperature
  • Visual Alarm Indication for: Pump Room Trouble
  • Pump On Demand
  • AC Power Failure
  • Charger 1-2 Failure
  • Battery 1-2
  • Weak
  • Battery 1-2 Overvoltage
  • Lossof Continuity on Starter 1-2
  • High Fuel Level
  • Fuel Tank Leak
  • PLD Low Suction Pressure
  • High Raw Water Temp
  • Low Pump Room Temp
  • High Pump Room Temp
  • ECM Warning
  • Weekly Test Cut-In Pressure Not Reached
  • Check Weekly Test Solenoid
  • Pressure Transducer Fault
  • Invalid Cut-In Pressure
  • Service Required Audible and Visible Alarm Indication for: Engine Trouble • Controller Trouble • Engine Low Oil Pressure • Engine High Temp. • Engine Low Temp. • Engine Overspeed • DC Failure • Battery 1-2 Failure • Engine Fail To Start • Low Fuel Level • ECM Fault • ECM SS In Alternate Position • Fuel Injection Malfunction

• DPDT 8A 250V Remote Alarm Contacts Are Provided For:

• Engine Run

• Common Controller Trouble (Charger Failure, Pressure Transducer Fault)

 • Common Engine Trouble (High Engine Temp., Fail To Start, Fuel Injection Malfunction, ECM Selector Switch in Alternate Position, Battery 1-2 Failure, DC Failure, Loss of Continuity to Starter 1-2, Engine Overspeed, Fail When Running, Low Oil Pressure, PLD Low Suction Pressure)

• Common Pump Room Trouble (Low Fuel Level, High Fuel Level, Fuel Tank Leak, Low / High Pump Room

Temperature, AC Power Failure, H-O-A Selector Switch in OFF or HAND)

• Modbus Communications with TCP/IP frame format and a shielded female RJ45 connector.

• Input Terminals for Connection to External Devices:

• Low Fuel Level

• Remote AUTOMATIC Start

• Deluge Valve Start (re-assignable)

• Fuel Tank Leak (re-assignable)

• High Fuel Level (re-assignable)

• Pump Room Ambient Temperature Switch, Display and Alarms